Details
MODEL | MDR-60-5 | MDR-60-12 | MDR-60-24 | MDR-60-48 | |
OUTPUT | DC VOLTAGE | 5V | 12V | 24V | 48V |
RATED CURRENT | 12A | 5A | 2.5A | 1.25A | |
CURRENT RANGE | 0 ~ 12A | 0 ~ 5A | 0 ~ 2.5A | 0 ~ 1.25A | |
RATED POWER | 50W | 60W | 60W | 60W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p | 200mVp-p | |
VOLTAGE ADJ. RANGE | 5 ~ 6V | 12 ~ 15V | 24 ~ 30V | 48 ~ 56V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.5% | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME Note.5 | 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load | ||||
HOLD UP TIME (Typ.) | 50ms/230VAC 20ms/115VAC at full load | ||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
EFFICIENCY (Typ.) | 78% | 86% | 88% | 87% | |
AC CURRENT (Typ.) | 1.8A / 115VAC 1A / 230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 30A / 115VAC 60A / 230VAC | ||||
LEAKAGE CURRENT | <1ma 240vac="" td=""> | ||||
PROTECTION | OVERLOAD | 105 ~ 150% rated output power | |||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | |||||
OVER VOLTAGE | 6.25 ~ 7.25V | 15.6 ~ 18V | 31.2 ~ 36V | 57.6 ~ 64.8V | |
Protection type : Shut down o/p voltage, re-power on to recover | |||||
FUNCTION | DC OK SIGNAL | Relay contact rating(max.): 30V / 1A resistive | |||
ENVIRONMENT | WORKING TEMP. | -20 ~ +70 (Refer to output load derating curve) | |||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85 , 10 ~ 95% RH | ||||
TEMP. COEFFICIENT | ±0.03% / (0 ~ 50) | ||||
VIBRATION | Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6 | ||||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | UL508, TUV EN60950-1 Approved | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms/500VDC 25 70%RH | ||||
EMI CONDUCTION & RADIATION | Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B | ||||
HARMONIC CURRENT | Compliance to EN61000-3-2,-3 | ||||
EMS IMMUNITY | Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3 heavy industry level, criteria A | ||||
OTHERS | MTBF | 299.2K hrs min. MIL-HDBK-217F (25) | |||
DIMENSION | 40*90*100mm (W*H*D) | ||||
PACKING | 0.33Kg; 42pcs / 14.8Kg / 0.82CUFT | ||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time. |
||||
Pictures, dimensions,table data and technical drawings of this product are made with reasonable care and liability is excluded for the accuracy and correctness of this data. |
Features
Features:
Block Diagram
Dimensions